How it is calculated
Heat demand is estimated from room volume: about 2.9 Btu/h per cu ft for a well insulated home, 3.9 for an average one and 4.8 for a poorly insulated one. Corner rooms get 20 % more. Radiator output is rated at a set temperature difference, so it is converted to your water temperature with the EN 442 formula. For whole-house sizing, a Manual J calculation is the standard.
Heat, Btu/h = length × width × height × (2.9, 3.9 or 4.8)Correction = (system ΔT ÷ rated ΔT)^1.3Catalog output = heat ÷ correctionExample
A 15 × 12 ft room with 8 ft ceilings in an average home needs about 5,600 Btu/h (1,630 W). With a boiler at 167/149 °F, a panel radiator rated at ΔT 50 K works at its catalog output, so choose one rated at 5,600 Btu/h or more.
Tips from practice
- Place radiators under windows to block cold drafts.
- With a heat pump, radiators need 2–3 times the catalog output you would need with a boiler.
- Bleed radiators each fall so air does not block the flow.
Questions and answers
How many BTU per square foot?
Roughly 25–40 Btu/h per sq ft with 8 ft ceilings, depending on insulation and climate.
What does ΔT 50 mean?
The difference between the radiator’s average temperature and the room air at which output is measured: 50 K, or 90 °F.
Why does a heat pump need bigger radiators?
The water is cooler, so each square foot of radiator gives off much less heat. The calculator corrects for it.